Permit Number: T08OT00634
Parcel: 11307147A

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T08OT00634
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/18/2008 LOREN MAKUS ENGINEERING REVIEW Approved March 18, 2008

The applicant is authorized to use a portion of the flood hazard area (SFHA Zone AE, Panel 1639) in the City of Tucson, Arizona, on the property described as 1300 East Fort Lowell Road for the purpose of making repairs to an existing multi-family residential structure

The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations require the issuance of an additional Floodplain Use Permit.

The following conditions shall apply to this permit.

1. All work shall conform to the approved improvement plans which are made part of this permit (T08CM00493) which is for improvements in an existing structure.

2. The improvements are not a substantial improvement. The appraised value of the existing structure is $241,920. The estimated cost of the improvements is $69,682.

3. Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties.

4. Any additional improvements not reflected in the current permit will be subject to separate review and additional permits.

5. This permit becomes invalid and is subject to additional floodplain review, if any required improvement permit(s') changes the configuration of the structure and or site development.

This Floodplain Use Permit will be automatically revoked and becomes invalid for non-compliance to conditions set forth in this permit.
The applicant is authorized by the City Engineer to receive a floodplain use permit subject to the above referenced conditions and restrictions.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/24/2008 VFLORES1 OUT TO CUSTOMER Completed