Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08EL01661
Parcel: 122060490

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL01661
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/28/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08EL01661 8/28/08

1. Scope of Work in the Description indicates the replacement of an existing meter pack. Drawing indicates the replacement of the entire service entrance, including service entrance conductors and grounding electrode system. Please clarify.
2. Size grounding electrode conductor per NEC TAble 250.66.
3. Provide available fault current at the service and fault current rating of new equipment.
4. Clarify whether existing service is rated for 600A.
5. clarify whether existing service entrance conductors are 350 MCM.
6. Ampacity of 350 MCM is only 310A. Provide load calculations.