Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T08EL01661
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/28/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T08EL01661 8/28/08 1. Scope of Work in the Description indicates the replacement of an existing meter pack. Drawing indicates the replacement of the entire service entrance, including service entrance conductors and grounding electrode system. Please clarify. 2. Size grounding electrode conductor per NEC TAble 250.66. 3. Provide available fault current at the service and fault current rating of new equipment. 4. Clarify whether existing service is rated for 600A. 5. clarify whether existing service entrance conductors are 350 MCM. 6. Ampacity of 350 MCM is only 310A. Provide load calculations. |