Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T08EL01463
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/08/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T08EL01463 8/5/08 1. Lighting fixtures are on Panel B. Show Panel B schedule. 2. Clarify arrowhead with no description, pointing to object on east exterior wall. 3. Show Panel A on line diagram, which only shows SES B. 4. Total VA for phases A and B appear to greatly exceed actual calculated loads. Same for the high leg amperage. 5. TEP Available Fault Current at metering equipment is 22,000A, per SR-510 for single phase, UG services 400A. |