Permit Number: T08EL01463
Parcel: 11104219C

Address:
3237 N RICHEY BL

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL01463
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08EL01463 8/5/08

1. Lighting fixtures are on Panel B. Show Panel B schedule.
2. Clarify arrowhead with no description, pointing to object on east exterior wall.
3. Show Panel A on line diagram, which only shows SES B.
4. Total VA for phases A and B appear to greatly exceed actual calculated loads. Same for the high leg amperage.
5. TEP Available Fault Current at metering equipment is 22,000A, per SR-510 for single phase, UG services 400A.