Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T08EL01241
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/14/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approv-Cond | T08EL01241 7/3/08 1. Ampacity of #3 conductor is 100A. Not Protected by the 125A Fuses. 2. Provide for the bond to be #4, not #6, on the Grounding System. Reference NEC Table 250.66. 3. TEP does not provide a single phase, 120/208V electrical service. 4. If this is an overhead 240V service, please note that TEP does not publish available fault current for this as a commercial service. SR-510 directs the reader to contact TEP for fault current. 5. Provide fault current rating of existing panel. 6. New overhead electrical service not permitted, per Section 11.1.1, City Amendments to IBC. Submit waiver, on attached form. |