Permit Number: T08EL01241
Parcel: 10601228C

Address:
3653 N 1ST AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL01241
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/14/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approv-Cond T08EL01241 7/3/08

1. Ampacity of #3 conductor is 100A. Not Protected by the 125A Fuses.
2. Provide for the bond to be #4, not #6, on the Grounding System. Reference NEC Table 250.66.
3. TEP does not provide a single phase, 120/208V electrical service.
4. If this is an overhead 240V service, please note that TEP does not publish available fault current for this as a commercial service. SR-510 directs the reader to contact TEP for fault current.
5. Provide fault current rating of existing panel.
6. New overhead electrical service not permitted, per Section 11.1.1, City Amendments to IBC. Submit waiver, on attached form.