Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08EL01186
Parcel: 11704201A

Address:
37 W 5TH ST

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL01186
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved