Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T08EL01186
Parcel: 11704201A

Address:
37 W 5TH ST

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL01186
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08EL01186 6/27/08

1. Provide to-scale plan view with location of all equipment.
2. Provide TEP fault current, fault calculations, and fault current rating of all equipment.
3. Clarify intent with respect to electrical panels. New with no load, existing with existing load, new with existing load terminated to new branch circuits, or what?
4. The bond on the line side of the service disconnect is sized at #2, not #4. NEC Table 250.122.
5. If this replaces an existing overhead service, state so on the plans. Otherwise apply for an underground to overhead waiver.