Permit Number: T08EL01182
Parcel: 13812049A

Address:
2 W VALENCIA RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08EL01182
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08EL01182 8/29/08

1. Revised plan is dated 8/14/08. However, so is the originally approved plan, and the initial approval is dated 8/25/08. thus it can not be that a revision to plans approved 8/25/08 be dated 8/14. Please revise, seal, and date plans according to the requirements of the Arizona State Board of Technical Registration.
2. Since the panel is being relocated directly adjacent to the service, the distance for Fault 2 is no longer 30'.
3. Fault calculations require panel to be rated 14K. Panel schedule specifies 10K. Please clarify and correct.