Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08EL01182
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/29/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08EL01182 8/29/08 1. Revised plan is dated 8/14/08. However, so is the originally approved plan, and the initial approval is dated 8/25/08. thus it can not be that a revision to plans approved 8/25/08 be dated 8/14. Please revise, seal, and date plans according to the requirements of the Arizona State Board of Technical Registration. 2. Since the panel is being relocated directly adjacent to the service, the distance for Fault 2 is no longer 30'. 3. Fault calculations require panel to be rated 14K. Panel schedule specifies 10K. Please clarify and correct. |