Permit Number: T08EL01182
Parcel: 13812049A

Address:
2 W VALENCIA RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08EL01182
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520.837.4907 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. It is not clear from the submittal materials that this location doesn't need to be Classified and designed according to the requirements of Chapter 5 of the National Electrical Code.
2. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 106.1.1, IBC 2006.
3. Size the Grounding Electrode Conductor on the Electrical Riser Diagram.
4. In Feeder on Keynote 1, please eliminate the redundant #6 GROUND as being redundant. In the event of a fault, the 4th 3/0 conductor will serve as the path back to the source.