Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T08EL01039
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/10/2008 | LBUCZYN1 | ELECTRICAL-RESIDENTIAL | REVIEW | Denied | T08EL01039 6/10/08 1. Please change the #2 Cu Grounding Electrode Conductor to 1/0. NEC Table 250.66. 2. Provide service disconnecting means. NEC 230.70. 3. Provide Service Equipment Overload Protection. NEC 230 Part VII. 4. Provide TEP available fault current. 5. Provide fault current rating of equipment. |