Permit Number: T08EL01039
Parcel: 12703452C

Address:
5842 E 3RD ST

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL01039
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2008 LBUCZYN1 ELECTRICAL-RESIDENTIAL REVIEW Denied T08EL01039 6/10/08

1. Please change the #2 Cu Grounding Electrode Conductor to 1/0. NEC Table 250.66.
2. Provide service disconnecting means. NEC 230.70.
3. Provide Service Equipment Overload Protection. NEC 230 Part VII.
4. Provide TEP available fault current.
5. Provide fault current rating of equipment.