Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T08EL00829
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T08EL00829 5/12/08 1. Provide City DSD Activity Numbers for all related construction work. 2. Show locations of job trailers on plans. 3. Show feeders and overcurrent protection for job trailers. 4. Show grounding at job trailers per NEC 250.32. 5. Provide TEP fault current. 6. Provide fault current rating of all equipment. 7. Show disconnecting means and ratings for job trailers. |