Permit Number: T08EL00671
Parcel: 11460019C

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL00671
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08EL00671 8/5/08

1. With a 70A CB on Revision 2, the Equipment Grounding Conductor needs to be #8, not #10.
2. Field inspector has indicated that load has been added to Panel B. Please verify with contractor if such is the case, and revise panel and plans as necessary. Otherwise, disregard.