Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T08EL00671
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/05/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T08EL00671 8/5/08 1. With a 70A CB on Revision 2, the Equipment Grounding Conductor needs to be #8, not #10. 2. Field inspector has indicated that load has been added to Panel B. Please verify with contractor if such is the case, and revise panel and plans as necessary. Otherwise, disregard. |