Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T08EL00419
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/14/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08EL00419 3/14/08 1. Load calculation violates NEC 220.84 because a demand factor of 40% has already been taken. Service calculation shall comply with NEC 220.84 (C). 2. Please revisit fault calculations. It appears that wire length is less than 30' on scaled drawing. Also please note that for a single phase commercial customer the available fault current at a 400A service would be limited to 22,000A only if the utility secondary were at minimum 45' in length. |