Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T08EL00356
Parcel: 11104191A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08EL00356
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/28/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Passed T08EL00356 4/28/08

1. See comments by Ray Majuta, 3/13/08, as pasted below.



Electrical comments; Drawing has been denied for the following items.


1.Under load calculations the following statement is made.
"recordings taken between June 28 and july 26.2005 indicate a maximum load of 680 a on the existing 600a service. The new service is sized at 800a."
This is an unreliable and inconclusive method of determining the load. There have been no permits taken out in the past under this address to indicate an increase in capacity for the service,I presume the increase has been caused by additional increase on the load side. Provide calculations for the feeders being connected to the new service.
2. Under the box titled "Existing Feeder Sizes" the ampacities for conductors have the over-current devices set too high, for example-----

# 2 AL GOOD AT 90AMPS OC DEVICE 100A
# 1/0 AL GOOD AT 120AMPS OC DEVICE 175A
# 2/0 AL GOOD AT 135AMPS OC DEVICE 200A
# 3/0 AL GOOD AT 155AMPS OC DEVICE 225A
# 4/0 AL GOOD AT 180AMPS OC DEVICE 250A.

#3. The 2/0 cu grounding electrode conductor appears too small for the 800 amp service.

Ray T Majuta
Development Service Department
Electrical Plan Exam
520-837-4988
Ray.Majuta@tucsonaz.gov
#3. The 2/0 cu grounding electrode conductor