Permit Number: T08EL00349
Parcel: 10321342A

Address:
2112 W GRANT RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL00349
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/07/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08EL00349 3/7/08

1. G-5B has 1080 VA, not 360.
2. G-18B has 360VA, not 180.
3. Don't see how dipping cabinet fits on the panel because all other A and B slots are full.
4. Recheck all loads and correct as appropriate.
5. G-5A has way more than 400VA with (12) 96W troffers, an A-19 and an exhaust fan.
6. G-17B starts out with 1145 VA for the track lighting and the down lights, can't make out the ceiling fans.