Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T08EL00349
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/07/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08EL00349 3/7/08 1. G-5B has 1080 VA, not 360. 2. G-18B has 360VA, not 180. 3. Don't see how dipping cabinet fits on the panel because all other A and B slots are full. 4. Recheck all loads and correct as appropriate. 5. G-5A has way more than 400VA with (12) 96W troffers, an A-19 and an exhaust fan. 6. G-17B starts out with 1145 VA for the track lighting and the down lights, can't make out the ceiling fans. |