Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T08EL00349
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/04/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08EL00349 3/4/08 1. For Circuits G-10,12 and G-3 Power Plan does not coordinate with panel schedule. Typical for any other instances which may apply. 2. Provide an electrical circuit for the receptacles by the Ac and the shelves. 3. Separate Circuits G-5 from B-17B on the Lighting Plan. |