Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T08EL00336
Parcel: 11903430A

Address:
3309 S 12TH AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL00336
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08EL00336 2/28/08

1. Specify the number of circuits on both new panels.
2. Since voltage is going from 240V to 208V, please demonstrate that no equipment rated for 240V will be reconnected to 208V.
3. Both disconnecting means at the gutter shall be connected to the Grounding Electrode System. Reference NEC 250.24 (B).
4. Grounding electrode system established at Panel B shall be bonded to the service grounding electrode system.
5. Any bond/GND on the line side of the service disconnecting means shall be sized according to NEC Table 250.66. So the #6 in the same conduit as the 3/0 shall be changed to a #4.
6. The #6 GROUND between the TEP transformer and the CT can is redundant.
7. Since Panel B has available fault current of only 5722A it is not necessary to series rate it 65/10K. And doing so would imply a 3-tiered rating, which is not available commercially.