Permit Number: T08EL00265
Parcel: 13220003A

Address:
3401 E GAS RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL00265
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08EL00265 2/15/08

1. Secondary on single phase transformer, consisting of 2 sets of #1 w/#4GND, may not be smaller than 1/0. Reference NEC 310.4.
2. Per NEC 250.28(D), please specify the size of the size of the Main Bonding Jumper at 4/0.