Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T08EL00265
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/15/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08EL00265 2/15/08 1. Secondary on single phase transformer, consisting of 2 sets of #1 w/#4GND, may not be smaller than 1/0. Reference NEC 310.4. 2. Per NEC 250.28(D), please specify the size of the size of the Main Bonding Jumper at 4/0. |