Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08EL00120 2/28/08

1. Submit a catalogue cut sheet for the RHH RWH direct bury cable. Demonstrate that this product is listed for direct burial.
2. May only use a listed means of bringing conductor from the service entrance to the junction box. An on-site fabricated chase shall not take the place of listed conduit. However, one may specify a larger conduit for all of the conductors.