Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08EL00120
Parcel: 106030780

Address:
219 W NAVAJO RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL00120
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved