Permit Number: T08EL00120
Parcel: 106030780

Address:
219 W NAVAJO RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL00120
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08EL00120 1/31/08

1. Turn in waiver to add new overhead electrical services, second floor.
6. Cooler is not subject to the demand factor. Reference NEC 220.82 (C). Please review this Code section.
3. Put furnace on load calculation for Panel 219A since it is on the Panel schedule.