Permit Number: T08EL00120
Parcel: 106030780

Address:
219 W NAVAJO RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL00120
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/22/2008 HEATHER THRALL ZONING REVIEW Approved
01/23/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T08EL00120 1/23/08

1. Provide a complete electrical design for the proposed upgrade.
2. Show existing equipment, along with its rating, and indicate which equipment is to be removed, which is to be reused, and any connection between new and existing.
3. Show the voltage, current, and fault current rating of new equipment.
4. Provide TEP available fault current.
5. Specify conduit and conductor size and type.
6. For the purposes of this permit, show the arrangement of how each building is to be powered. Clarify which buildings are occupied and which are unoccupied at this time.