Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T08EL00120
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/22/2008 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 01/23/2008 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T08EL00120 1/23/08 1. Provide a complete electrical design for the proposed upgrade. 2. Show existing equipment, along with its rating, and indicate which equipment is to be removed, which is to be reused, and any connection between new and existing. 3. Show the voltage, current, and fault current rating of new equipment. 4. Provide TEP available fault current. 5. Specify conduit and conductor size and type. 6. For the purposes of this permit, show the arrangement of how each building is to be powered. Clarify which buildings are occupied and which are unoccupied at this time. |