Permit Number: T08EL00111
Parcel: 13336008R

Address:
700 N BONANZA AV

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T08EL00111
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/31/2008 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T08CM00111 7/31/08

1. Registrant shall date seal, and indicate expiration date as well. per Arizona Revised Statutes.
2. Please revise "NEC 408.2 (A)(3)" to read "NEC 408.3 (A) (3)."
3 Minimum font size is 1/8". Please blow up fault calculations and Grounding Electrode Conductor sizing diagram for better resolution and documentation.