Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T08CM04020
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/25/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide information to show that the hub drain (P1.0 and Riser 1A) complies with Sections 411.1 and 804.1, UPC 2006. 2. Indirect waste receptors shall be installed in readily accessible locations for inspection and cleaning (i.e. does the "hub drain" located under the cabinet meet these requirements?). Reference: Sections 203.0 (definition, accessible) and 804.1, UPC 2006. |
| 03/25/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson (i.e. the minimum size for a condensate drain serving two or more units, up to 20-tons of total capacity, is 1"). [Show the size, routing, and termination of the condensate drains for AC1-1, AC1-2, AC2-1, and AC3-1. Reference: Sections 307.2 and 307.2.2, IMC 2006 as amended by the City of Tucson. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/30/2011 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |