Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 3RD
Permit Number - T08CM04020
Review Name: REVISION - - 3RD
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 02/17/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Riser diagram 20/P4.1 does not comply with the requirements of Sections 311.4 and 908.1, UPC 2006. 2. Provide a cleanout at the base of each roof drain leader prior to its connection with the horizontal storm drain. Reference: Section 1101.12.2, UPC 2006. |
| 02/17/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Show the size, routing, and termination of the condensate drains for AC1-1, AC1-2, AC2-1, and AC3-1. Reference: Sections 307.2 and 307.2.2, IMC 2006 as amended by the City of Tucson. |
| 02/22/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 03/09/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/16/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 03/16/2011 | SUE REEVES | REJECT SHELF | Completed |