Permit Number: T08CM04020
Parcel: 12810076B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM04020
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2009 DAVE MANN FIRE REVIEW Approved
04/20/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/21/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
04/23/2009 GERRY KOZIOL WWM REVIEW Denied need to build public sewer
need to show location/method of connection to public sewer
05/05/2009 RICK MYERS PLUMBING-COMMERCIAL REVIEW Denied Comment still not resolved: riser diagrams 2/P4.0, 2A/4.0, 4A/P4.0, 5/P4.0, 7/P4.0, 8/P4.0, 10/P4.1, 11/P4.1, 13/P4.1, 15/P4.1, and 19/P4.1, do not reflect the fixture, vent, or stack arrangements, or the pipe sizes shown on the plumbing floor plans. coordinate the riser diagrams shown on sheets P4.0, and P4.1 with the plumbing floor plans. Reference: Section 103.2.3, 2006 UPC.
05/06/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the installation of EF-8 complies with the requirements of Section 506.3.12.3, IMC 2006.
2. Clarify the type of wall located on the west side of the proposed location for the Type I hood; it appears to be a type L wall which has wood studs. To comply with the requirements of Section 507.9, IMC 2006, a zero-clearance wall within 18" of a Type I hood shall have non-combustible supports and a smooth, non-absorbent, non-combustible material between the hood and the gypsum wall board.
05/06/2009 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/20/2009 SUE REEVES OUT TO CUSTOMER Completed
05/20/2009 SUE REEVES REJECT SHELF Completed