Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM04020
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/27/2009 | DAVE MANN | FIRE | REVIEW | Denied | Please include the following design criteria to the plans. 1. Flow data (static pressure, residual pressure, GPM) Available from the Fire Department (520) 791-3234 2. The hazard classification of the building, including any special hazards. 3. The density required and area of operation. |
| 02/27/2009 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | PREVIOUS COMMENT NUMBER: NUMBER 5, SHEET A0.1: "ACCESSIBILITY FACILITIES", PLEASE REFERENCE 2006 IBC CHAPTER 1 AND ICC ANSI 117.1. NUMBER 6, SHEET NOS. A3.0, A4.1, A5.2, A9.5, "S" DRAWINGS, "ID" DRAWINGS AND MANY OTHERS: AS PER DSD WEB PAGE, PERMIT REVIEW INFORMATION, THE MINIMUM DRAWING LETTERING FONT REQUIREMENTS ARE DESCRIBED. PLEASE COMPLY, ALL DRAWINGS. NUMBER 7, SHEET A0.1, SPRINKLER SYSTEMS: A LETTER OF DEFERRAL NOTIFICATION TO THE BUILDING OFFICIAL, MR. JESSIE SANDERS SHALL BE SUBMITTED FOR THE SPRINKLER SYSTEM SUBMITTAL DEFERRAL AND A COPY IS TO BE PRESENTED WITH THE PERMIT SUBMITTAL. |
| 03/02/2009 | RONALD BROWN | ZONING HC SITE | REVIEW | Denied | SEE BUILDING-COMMERICAL COMMENTS |
| 03/04/2009 | GERRY KOZIOL | WWM | REVIEW | Denied | need to show location/method of connection to public sewer |
| 03/12/2009 | ROBERT SHERRY | WATER | REVIEW | Denied | Comment not resolved; provide reference copies of the civil drawings with the next submittal. Provide a site drawing showing the location of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006. |
| 03/12/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not resolved; provide reference copies of the civil drawings with the next submittal. Provide a site drawing showing the size and route of the building water supply along with the location of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006. 2. Comment not resolved; provide reference copies of the civil drawings with the next submittal. Provide a site drawing showing the size; slope, and route of the building sewer. Reference: Section 103.2.3, UPC 2006. 3. Comment not resolved; provide reference copies of the civil drawings with the next submittal. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson. 4. Comment not resolved, riser diagrams 2/P4.0, 2A/P4.0, 4/P4.0, 4A/P4.0, 5/P4.0, 7/P4.0, 8/P4.0, 10/P4.1, 11/P4.1, 13/P4.1, 15/P4.1, and 19/P4.1 do not reflect the fixture, vent or stack arrangements or the pipe sizes shown on the plumbing floor plans. Riser diagram 14/P4.1 does not seem to be shown on the plumbing floor plans. Also, riser diagrams 2/P4.0 and 4/P4.0 do not appear to be complying with the requirements of Section 711.0, UPC 2006. Coordinate the riser diagrams shown on sheets P4.0 and P4.1 with the plumbing floor plans. Reference: Section 103.2.3, UPC 2006. 5. Comment not resolved, revise the water fixture calculations to include the 103 domestic dishwashers shown on the architectural plans. Coordinate the water and waste load calculations with the plumbing plans. Reference: Section 103.2.3, UPC 2006. 6. Comment not resolved. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps will require backflow preventers. Specify the type of backflow prevention device required for each water connection. Refer to Table 6-2, UPC 2006 for determination of the appropriate type of backflow protection for each appliance. The Watts series 7 is listed for non-health hazard residential water system containment, continuous pressure applications. The eyewash station (EEW) is a plumbing fixture, not an appliance, and it does not require backflow protection. Reference: Section 603.0, UPC 2006, as amended by the City of Tucson. |
| 03/13/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Complete the design for the exhaust of the Type I hood located in the room 173 (EF-8) to comply with the requirements of Sections 506, 507, and 508, IMC 2006. Drawings shall be sealed by an Arizona registrant. 2. Clarify the installation of EF-8. The schedule calls out a wall-mounted fan that is ceiling-mounted with a roof curb and a vented curb extension. Reference: Section 106.3.1, IMC 2006. 3. The walls adjacent to the hood have combustible supports (wood studs); show how this complies with the requirements of Section 507.9, IMC 2006. |
| 03/17/2009 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 03/20/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 03/23/2009 | STEVE SHIELDS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/08/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 04/08/2009 | SUE REEVES | REJECT SHELF | Completed |