Permit Number: T08CM04020
Parcel: 12810076B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM04020
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2009 DAVE MANN FIRE REVIEW Denied Please include the following design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 791-3234
2. The hazard classification of the building, including any special hazards.
3. The density required and area of operation.
02/27/2009 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied PREVIOUS
COMMENT
NUMBER:

NUMBER 5, SHEET A0.1: "ACCESSIBILITY FACILITIES", PLEASE REFERENCE 2006 IBC CHAPTER 1 AND ICC ANSI 117.1.

NUMBER 6, SHEET NOS. A3.0, A4.1, A5.2, A9.5, "S" DRAWINGS, "ID" DRAWINGS AND MANY OTHERS: AS PER DSD WEB PAGE, PERMIT REVIEW INFORMATION, THE MINIMUM DRAWING LETTERING FONT REQUIREMENTS ARE DESCRIBED. PLEASE COMPLY, ALL DRAWINGS.

NUMBER 7, SHEET A0.1, SPRINKLER SYSTEMS: A LETTER OF DEFERRAL NOTIFICATION TO THE BUILDING OFFICIAL, MR. JESSIE SANDERS SHALL BE SUBMITTED FOR THE SPRINKLER SYSTEM SUBMITTAL DEFERRAL AND A COPY IS TO BE PRESENTED WITH THE PERMIT SUBMITTAL.
03/02/2009 RONALD BROWN ZONING HC SITE REVIEW Denied SEE BUILDING-COMMERICAL COMMENTS
03/04/2009 GERRY KOZIOL WWM REVIEW Denied need to show location/method of connection to public sewer
03/12/2009 ROBERT SHERRY WATER REVIEW Denied Comment not resolved; provide reference copies of the civil drawings with the next submittal. Provide a site drawing showing the location of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006.
03/12/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved; provide reference copies of the civil drawings with the next submittal. Provide a site drawing showing the size and route of the building water supply along with the location of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006.
2. Comment not resolved; provide reference copies of the civil drawings with the next submittal. Provide a site drawing showing the size; slope, and route of the building sewer. Reference: Section 103.2.3, UPC 2006.
3. Comment not resolved; provide reference copies of the civil drawings with the next submittal. Provide the rim elevation of the next upstream sanitary manhole and the first floor elevation. Determine the need for a backwater valve per Section 710.1, UPC 2006, as amended by the City of Tucson.
4. Comment not resolved, riser diagrams 2/P4.0, 2A/P4.0, 4/P4.0, 4A/P4.0, 5/P4.0, 7/P4.0, 8/P4.0, 10/P4.1, 11/P4.1, 13/P4.1, 15/P4.1, and 19/P4.1 do not reflect the fixture, vent or stack arrangements or the pipe sizes shown on the plumbing floor plans. Riser diagram 14/P4.1 does not seem to be shown on the plumbing floor plans. Also, riser diagrams 2/P4.0 and 4/P4.0 do not appear to be complying with the requirements of Section 711.0, UPC 2006. Coordinate the riser diagrams shown on sheets P4.0 and P4.1 with the plumbing floor plans. Reference: Section 103.2.3, UPC 2006.
5. Comment not resolved, revise the water fixture calculations to include the 103 domestic dishwashers shown on the architectural plans. Coordinate the water and waste load calculations with the plumbing plans. Reference: Section 103.2.3, UPC 2006.
6. Comment not resolved. Appliances to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps will require backflow preventers. Specify the type of backflow prevention device required for each water connection. Refer to Table 6-2, UPC 2006 for determination of the appropriate type of backflow protection for each appliance. The Watts series 7 is listed for non-health hazard residential water system containment, continuous pressure applications. The eyewash station (EEW) is a plumbing fixture, not an appliance, and it does not require backflow protection. Reference: Section 603.0, UPC 2006, as amended by the City of Tucson.
03/13/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Complete the design for the exhaust of the Type I hood located in the room 173 (EF-8) to comply with the requirements of Sections 506, 507, and 508, IMC 2006. Drawings shall be sealed by an Arizona registrant.
2. Clarify the installation of EF-8. The schedule calls out a wall-mounted fan that is ceiling-mounted with a roof curb and a vented curb extension. Reference: Section 106.3.1, IMC 2006.
3. The walls adjacent to the hood have combustible supports (wood studs); show how this complies with the requirements of Section 507.9, IMC 2006.
03/17/2009 JASON GREEN ENGINEERING REVIEW Approved
03/20/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
03/23/2009 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
04/08/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
04/08/2009 SUE REEVES REJECT SHELF Completed