Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM04004
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/13/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Completed | |
| 01/13/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 01/13/2009 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/13/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for business occupancy (i.e. drinking fountain; bottled water will not be accepted as a substitute). Reference: Section 1109.5, IBC 2006. 2. The break room sink is not a private bar sink; Calculate the water and waste fixture units using the fixture units shown in Tables 6-5 (or A-2) and 7-3, UPC 2006. 3. Revise the water calculations to include the static pressure loss due to lift. Reference: Section 610.0, UPC 2006. 4. Provide calculations for the sizing of the domestic water tubing to show that the specified pipe sizes will result in the friction and velocity requirements specified in the water calculations. Reference: Section 103.2.3 and 610.0, UPC 2006. 5. Clarify the support requirements for the domestic water piping as noted in plumbing general note 3 in light of the specified tubing for the domestic water. Reference: Sections 103.2.3 and 314.0, UPC 2006. 6. Revise the size of the drain piping for the lavatory. Reference: Section 703.2, UPC 2006. |
| 01/14/2009 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 01/14/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/30/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | PLEASE SUBMIT STRUCTURAL CALCULATIONS AND STRUCTURAL CONNECTION DETAILS FOR HVAC UNIT ON ROOF |
| 12/30/2008 | DAVE MANN | FIRE | REVIEW | Approved | |
| 12/30/2008 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/30/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/14/2009 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 01/14/2009 | SUE REEVES | REJECT SHELF | Completed |