Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM04004
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
01/13/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
01/13/2009 ROBERT SHERRY WATER REVIEW Approved
01/13/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2006, for business occupancy (i.e. drinking fountain; bottled water will not be accepted as a substitute). Reference: Section 1109.5, IBC 2006.
2. The break room sink is not a private bar sink; Calculate the water and waste fixture units using the fixture units shown in Tables 6-5 (or A-2) and 7-3, UPC 2006.
3. Revise the water calculations to include the static pressure loss due to lift. Reference: Section 610.0, UPC 2006.
4. Provide calculations for the sizing of the domestic water tubing to show that the specified pipe sizes will result in the friction and velocity requirements specified in the water calculations. Reference: Section 103.2.3 and 610.0, UPC 2006.
5. Clarify the support requirements for the domestic water piping as noted in plumbing general note 3 in light of the specified tubing for the domestic water. Reference: Sections 103.2.3 and 314.0, UPC 2006.
6. Revise the size of the drain piping for the lavatory. Reference: Section 703.2, UPC 2006.
01/14/2009 GERRY KOZIOL WWM REVIEW Approved
01/14/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/30/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied PLEASE SUBMIT STRUCTURAL CALCULATIONS AND STRUCTURAL CONNECTION DETAILS FOR HVAC UNIT ON ROOF
12/30/2008 DAVE MANN FIRE REVIEW Approved
12/30/2008 MICHAEL ST. PAUL ZONING REVIEW Approved
12/30/2008 RONALD BROWN ZONING HC SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/14/2009 CINDY AGUILAR OUT TO CUSTOMER Completed
01/14/2009 SUE REEVES REJECT SHELF Completed