Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03995
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/15/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
01/15/2009 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
01/20/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE CALCULATIONS OR A LETTER STAMPED/SIGNED/DATED BY A LICENSED STRUCTURAL ENGINEER CERTIFYING THAT THE EXISTING STRUCTURE WILL ADEQUATELY SUPPORT THE NEW MECHANICAL UNITS PLACED ON THE FLOOR OR ROOF MEMBERS. IF SECTIONS OR DETAILS ARE REQUIRED, PROVIDE THOSE ON FULL SIZED SHEETS THAT ARE STAMPED/SIGNED/DATED BY A LICENSED STRUCTURAL ENGINEER. |
01/20/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T08CM03995 4415 E Grant Rd HVAC Upgrade Electrical plans denied for following: 1.Sheet E-3, new panel schedule, since existing feeders to unit panels is on #8, thge circuit breakers should be 50 amp. 2.Also the conductor shown in new panel should be a #8. 3.Sheet E-3, on the detail at Building Wiring, will the Exixting Distribution Panel now be a junction box? Is there avalibity to land the new conductors for the new panels. 4. Also under the item above it should be noted "Two Sets Of 4/0 feeders for Bldg B<G and F. 5.The plan shows for the new panel to be mounted on the side of the existing panel ? Ray T Majuta DSD City of Tucson Elect Plan Ck 1-20-09 520-837-4988 |
02/05/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
02/05/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide auxiliary drain pans, secondary drain systems, or water level detection devices for fan coil units. Reference: Section 307.2.3 IMC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/06/2009 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
02/06/2009 | SUE REEVES | REJECT SHELF | Completed |