Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM03994
Parcel: 13304009C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03994
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/16/2010 MARTIN BROWN FIRE REVIEW Denied Unable to locate response letter to previuos comments, which were:

No Parking - Fire Lane signs required. See Appendix D of the C.O.T. amendments to the 2006 IFC for location and spacing requirements.
Also, please relocate Fire Deparment Connection out from under the canopy.
06/16/2010 GERRY KOZIOL WWM REVIEW Denied NEED COT PERMIT FOR ON-SITE PRIVATE SEWER(MULTIPLE BUILDINGS WITH PRIVATE SEWER MANHOLES)- NEED DEQ REVIEW & APPROVAL OF ON-SITE PRIVATE SEWER- NEED 3RD FLOOR WASTEWATER REVIEW & APPROVAL OF CONSTRUCTING A NEW MANHOLE OVER AN EXSISTING 24" PUBLIC SEWER- NEED COPY OF ON-SITE PRIVATE SEWER FOR BASE MAP UPDATE
NEED TO PERMIT SEPTIC TO SEWER FOR EXSISTING BUILDINGS #1 THRU #7.
06/21/2010 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 06/21/2010,

The subject submittal has been reviewed. It can not be approved at this time. Address the following comments before the next submittal:

1- Revise the proposed building minimum finished floor elevation to 2542.85' as required by Floodplain Use Permit #T09OT01433.
2- This project is required to submit two elevation certificates (El Cert's) as stated in Condition #5 of Floodplain Use Permit #T09OT01433. Ensure that a preslab El Cert is completed and submitted to the Planning and Development Services Department (PDSD) before the slab is poured. Another El Cert is also required to be submitted to PDSD for the completed structure before the issuance of a certificate of occupancy.
06/22/2010 TERRY STEVENS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2010 CPIERCE1 OUT TO CUSTOMER Completed
09/09/2010 SUE REEVES REJECT SHELF Completed