Permit Number: T08CM03994
Parcel: 13304009C

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM03994
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2009 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; East District; 16,568 Square Foot Multi-Purpose Building; $104,660.35
03/10/2009 ROBERT SHERRY WATER REVIEW Approved
03/10/2009 MARTIN BROWN FIRE REVIEW Denied No Parking - Fire Lane signs required. See Appendix D of the C.O.T. amendments to the 2006 IFC for location and spacing requirements.
Also, please relocate Fire Deparment Connection out from under the canopy.
03/12/2009 GERRY KOZIOL WWM REVIEW Denied 1:The Academy of Tucson-Multipurpose building #8 D08-0035- school@sfr rate
2:Need COT permit for on-site private sewer(multiple buildings with private sewer manhole)- need DEQ review & approval of on-site private sewer- need 3rd floor wastewater review & approval of constructing a new manhole over exsisting 24" public sewer- need copy of on-site private sewer for base map update.
3: need to permit septic to sewer for exsisting buildings#1 through #7.
03/13/2009 TERRY STEVENS ZONING REVIEW Denied 03/13/2009

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming.
03/25/2009 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 03/25/2009,

The proposed building will be within the Tanque Verde Wash 100-year Floodplain. A Floodplain Use Permit is required before the building can be approved.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
06/15/2010 SUE REEVES REJECT SHELF Completed