Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03976
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2009 | THAUSER1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 01/02/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 12/26/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/26/2008 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 12/26/2008 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 12/26/2008 | ERIC NEWCOMB | ZONING HC SITE | REVIEW | Approved | |
| 12/31/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. If hot water will be supplied, show how the temperature of the hot water supply to the public lavatories will be controlled to a maximum temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 2. Provide a floor drain in the restroom. Reference: Section 411.2, UPC 2006. 3. Calculate the water demand using the fixture units shown in Tables 6-5 or A-2. Reference: Section 610.3, UPC 2006. 4. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for business occupancy (e.g. a service sink and a drinking fountain). |
| 12/31/2008 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide the size of the existing water meter and the total connected water demand that will result from the addition of this activity. The maximum demand that Tucson Water will allow with a 1" meter is 25 GPM. Reference: Sections 610.1 and 610.2, UPC 2006. 2. Verify that the water meter can be located in the basement of the building. 3. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Confirm that the basement location is acceptable to Tucson Water. Reference: COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf 4. If the backflow preventer is to be located in the basement, show how the drainage from the assembly will be accommodated. Reference: Section 603.3.9, UPC 2006. |
| 12/31/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approv-Cond | Deferred submittal: 1. Mechanical A/C units, 2. Elevator equipment room A/C, 3. Condensate drains (size, route, and termination) for all mechanical units. 4. Exhaust fans and ducts for restrooms |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/02/2009 | THAUSER1 | OUT TO CUSTOMER | Completed |