Permit Number: T08CM03970
Parcel: 13727633C

Address:
1795 W DREXEL RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03970
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/29/2009 MICHAEL ST. PAUL ZONING REVIEW Passed
01/30/2009 DAVE MANN FIRE REVIEW Approved
02/05/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
02/20/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the energy code compliance calculations to correspond to the specified construction of the building envelope (e.g. exterior walls not furred) and for the correct climate zone (i.e. Pima County < 4,000 feet). Reference: Section 101.4, International Energy Conservation Code 2006.
02/20/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. "Trap Guard" accessories are not approved for use in lieu of trap primers or a local hose bibb. Reference: Section 1002.4, IPC 2006.
2. The water pressure calculations are based on a static lift of five feet but according to the civil drawings, the first floor elevation is approximately five feet above the meter level. Revise the calculation to include the additional lift from the FFE to the highest water outlet. Reference: Section E103.2.2 (2), IPC 2006.
3. Show that there is adequate clearance and access for the 4" cleanout for S-1 in the millwork of classroom 103. Reference: Sections 708.8 and 708.9, IPC 2006.
4. Provide calculations to show that the size of the roof gutters for the main roof sections are adequate to provide drainage without overflowing. Reference: Section 1106.6, IPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/24/2009 CPIERCE1 OUT TO CUSTOMER Completed
02/24/2009 SUE REEVES REJECT SHELF Completed