Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM03970
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/29/2009 | MICHAEL ST. PAUL | ZONING | REVIEW | Passed | |
01/30/2009 | DAVE MANN | FIRE | REVIEW | Approved | |
02/05/2009 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
02/20/2009 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the energy code compliance calculations to correspond to the specified construction of the building envelope (e.g. exterior walls not furred) and for the correct climate zone (i.e. Pima County < 4,000 feet). Reference: Section 101.4, International Energy Conservation Code 2006. |
02/20/2009 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. "Trap Guard" accessories are not approved for use in lieu of trap primers or a local hose bibb. Reference: Section 1002.4, IPC 2006. 2. The water pressure calculations are based on a static lift of five feet but according to the civil drawings, the first floor elevation is approximately five feet above the meter level. Revise the calculation to include the additional lift from the FFE to the highest water outlet. Reference: Section E103.2.2 (2), IPC 2006. 3. Show that there is adequate clearance and access for the 4" cleanout for S-1 in the millwork of classroom 103. Reference: Sections 708.8 and 708.9, IPC 2006. 4. Provide calculations to show that the size of the roof gutters for the main roof sections are adequate to provide drainage without overflowing. Reference: Section 1106.6, IPC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
02/24/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
02/24/2009 | SUE REEVES | REJECT SHELF | Completed |