Permit Number: T08CM03970
Parcel: 13727633C

Address:
1795 W DREXEL RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T08CM03970
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2009 GERRY KOZIOL WWM REVIEW Approved
01/06/2009 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/06/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify which plumbing code is being used for this activity; sheet T0.01 specifies the UPC but the plumbing sheets reference the IPC. Use of the IPC will require an appeal to the Building Official.
01/06/2009 ROBERT SHERRY WATER REVIEW Approved
01/07/2009 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Each roof top air conditioning unit is equipped with a power exhaust to allow the modulation of the outside air while maintaining the building pressurization. As a result, RTU-1, RTU-2, and RTU-4 all circulate 2100 CFM through the return ducts and the exception to Section 606.2, IMC 2006 that exempts units returning 2,000 CFM or less from the smoke detector requirement is not applicable.
2. Provide energy code compliance calculations for the building envelope. Reference: Section 101.4, International Energy Conservation Code 2006.
01/13/2009 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/26/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. DEFERRED SUBMITTALS MUST BE APPROVED BY THE BUILDING OFFICIAL.
2. STRUCTURAL CALCULATIONS PAGE 10: MOMENT FRAME REFERS TO COMPUTER CALCULATIONS. PROVIDE THOSE.
3. SHEET S2.1; SCHEDULES: IS THIS A "BRICK" WALL SCHEDULE OR A BLOCK WALL? CLARIFY.
4. SHEET S3.1; CALCULATIONS: DID NOT FIND CALCULATIONS FOR LINTELS. PROVIDE.
5. SHEET S3.1; CALCULATIONS: DID NOT FIND CALCULATIONS FOR LEDGERS. PROVIDE.
6. SHEET S4.1; SECTION 106: NOTE TO LEFT OF WALL INDICATES "CONCRETE STEM WALL", WHILE NOTE TO RIGHT INDICATES "BRICK WALL". IS THIS BLOCK? CLARIFY.
7. SHEET S4.1; SECTION 104: "BRICK" OR BLOCK? CLARIFY.
8. SHEET S4.1; SECTION 106: WALL INDICATES #4 VERTICALS AT 16" OC WHILE SCHEDULE ON SHEET S2.1 INDICATES #5 AT 16" OC. CLARIFY.
9. SHEET S4.1; CALCULATIONS: DID NOT FIND CALCULATIONS FOR LINTELS. PROVIDE.
10. SHEET A1.00; ARCHITECTURAL FLOOR PLAN: UNDER "PARTITION TYPES", WALL A MUST MEET CRITERIA OF 2006 IBC SECTION 1607.13. PROVIDE DETAILS INDICATING BRACING AT TOP OF WALL, INCLUDING BRACE SIZE AND SPACING, BRACE CONNECTION TO TOP OF WALL AND TO ROOF STRUCTURE. PROVIDE CONNECTION OF WALL TO FLOOR SLAB.
12/26/2008 MARTIN BROWN FIRE REVIEW Denied Please provide site plan showing existing fire hydrant location(s). Hydrant should be within 500' (as the hose lays - around obstructions, etc.) of all parts of the new building. A new hydrant may be required.
12/30/2008 BIANCA RAMIREZ ENGINEERING REVIEW Approved
12/30/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/15/2009 THAUSER1 OUT TO CUSTOMER Completed
01/15/2009 SUE REEVES REJECT SHELF Completed