| 01/23/2009 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 8160 E Houghton Rd #130 Dential Office Denied for the following item: The water heater per the plumbing plan shows a single element of 3 kw, it would draw 25 amps at 120 volts or 14.4 amps at 208 volts. This has not been addressed. Ray T Majuta DSD City of Tucson Electrical Plan Ck 1/23/09 520-837-4988 |