Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03955
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/23/2008 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: 8160 E Houghton Rd #130 T08CM03955 Dental T I This project has had the electrical plans denied for the following items, please review and indicate independently how each has been addressed. 1. Provide a total building service load which includes this tenant load, this is required as per The Commercial Submittal Requirements. 2.Assign correct circuit numbers to all receptacles,lights,equipment and so forth. Now some circuits are assigned to CC which appears to be panel A-3. 3. Circuit 11 in Panel A-3 for the water heater is showing a load above 20 amps. 4. Where are circuits 1,3,5,and 7 as indicated in panel A-3. they seem to be for another use not shown on plan. 5. Power plan shows circuit CC-9 for X-ray1, at compressor location. This compressor should be labeled A-3 2,4. 6. Provide Interior Light Budget Calculations per IECC, 2006 as required by Commercial Submittal Requirements. 7. Some lighting on lighting plan does not show switching. 8. Exit and emergency fixtures are not circuited. Ray T Majuta Electrical Plan Ck DSD City Of Tucson, 12-24-08 520-837-4988 |
| 12/23/2008 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/26/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/29/2008 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/29/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Coordinate riser diagrams B and C with the piping layout shown on the plumbing plan. Reference: Section 103.2.3, UPC 2006. 2. Revise the water heater detail (E/P2.1) to reflect how the hot water return piping is to be connected to CW inlet to the water heater. (The specified water heater has HW two outlets but only one CW inlet connection.) Reference: Sections 103.2.3 and 501.0, UPC 2006. 3. Coordinate the electrical requirements for the water heater (3kW) with the electrical drawings. Reference: Sections 103.2.3 and 501.0, UPC 2006. 4. Appliances (e.g. vacuum pump) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Table 6-3, UPC 2006 require backflow prevention. Reference: Sections 602.3, 603.0, and Table 6-2, UPC 2006. |
| 12/29/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information to show how the condensate drain system has been sized. Reference: Section 307.2.2, IMC 2006, as amended by the City of Tucson. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/30/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 12/30/2008 | SUE REEVES | REJECT SHELF | Completed |