Permit Number: T08CM03928
Parcel: 12803076A

Review Status: Completed

Review Details: OTHER

Permit Number - T08CM03928
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/23/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The make up air unit, EC-1, is now scheduled to provide 2,400 CFM and the Kitchen hood schedule now calls for 3,000 CFM at the eyebrow supply plenum. Where is the other 600 CFM coming from? Reference Sections 106.3.1 and 508.1, IMC 2006.
2. Provide the size of the existing grease exhaust duct that is to be reused. Reference Sections 106.3.1 and 506.3.4, IMC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/23/2008 CINDY AGUILAR OUT TO CUSTOMER Completed