Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T08CM03928
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/23/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The make up air unit, EC-1, is now scheduled to provide 2,400 CFM and the Kitchen hood schedule now calls for 3,000 CFM at the eyebrow supply plenum. Where is the other 600 CFM coming from? Reference Sections 106.3.1 and 508.1, IMC 2006. 2. Provide the size of the existing grease exhaust duct that is to be reused. Reference Sections 106.3.1 and 506.3.4, IMC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/23/2008 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |