Permit Number: T08CM03928
Parcel: 12803076A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03928
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/18/2008 STEVE SHIELDS ZONING REVIEW Approved
12/18/2008 LOREN MAKUS ENGINEERING REVIEW Approved
12/18/2008 ERIC NEWCOMB ZONING HC SITE REVIEW Passed
12/18/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
12/18/2008 ERIC NEWCOMB ADA REVIEW Passed
12/19/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify how the hood is being connected to the building structure (i.e. where is the roof deck?) and increase the font size foe the hood connection detail. Reference: Section 302.1, IMC 2006.and section 106.1.1, IBC 2006.
2. Show that the make up air duct within 18" of the Type I exhaust hood complies with the requirements of Section 506.3.1.2, IMC 2006.
3. The make up air unit is scheduled to provide 3,000 CFM but the shop drawing calls for only 2,400 CFM at the eyebrow supply plenum. Where is the other 600 CFM being directed? Reference Sections 106.3.1 and 508.1, IMC 2006.
4. Provide a legible copy of the hood shop drawing with an acceptance stamp from the architect. Reference Section 106.3.1, IMC 2006.
5. Provide information to show that the operation of the Type I hood and the hood exhaust fan complies with Section 507.2.1.1, IMC 2006.
12/19/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/19/2008 ROBERT SHERRY WATER REVIEW Approved
12/19/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
12/19/2008 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
12/23/2008 CARL SCHULTZ FIRE REVIEW Approved
12/23/2008 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed