Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM03914
Parcel: 137055380

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03914
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/23/2008 VFLORES1 WWM REVIEW Approved
12/23/2008 RONALD BROWN ZONING HC SITE REVIEW Approved
12/29/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide structural calculations and details to show that the Type I hood and the two rooftop air conditioning units are supported from the building structure in accordance with Sections 302.1 and 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
2. The evaporative cooler supplies only 1575 CFM of make up air for the hood. If the remaining make up air is to be provided by an air conditioning unit, show that the roof top air-conditioning unit supplying the make up air for the kitchen hood is electrically interlocked to the exhaust fan. Reference: Section 508.1, IMC 2006.