Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T08CM03914
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/07/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
12/23/2008 | VFLORES1 | WWM | REVIEW | Approved | |
12/23/2008 | RONALD BROWN | ZONING HC SITE | REVIEW | Approved | |
12/29/2008 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations and details to show that the Type I hood and the two rooftop air conditioning units are supported from the building structure in accordance with Sections 302.1 and 507.6, IMC 2006. Reference: Section 302.1, IMC 2006. 2. The evaporative cooler supplies only 1575 CFM of make up air for the hood. If the remaining make up air is to be provided by an air conditioning unit, show that the roof top air-conditioning unit supplying the make up air for the kitchen hood is electrically interlocked to the exhaust fan. Reference: Section 508.1, IMC 2006. |