Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T08CM03894
Parcel: 127021890

Address:
5362 E 4TH ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM03894
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2009 GERRY KOZIOL WWM REVIEW Approved
02/09/2009 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 2-10-09
Activity: T08CM03894
Address: 5362 E. 4th St.
Applicant: Jeffrey Adragna

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Provide two copies of the corrected set of drawings (no clouds or revision numbers please) along with a set of the first submission (cloud corrections on this set please). All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

STRUCTURAL PLANS:
2. Specify current hardware equivalency to model numbers out of production (PHD2 has been discontinued).

SECTIONS - DETAILS:
3. Ceiling gypsum board must be either 5/8" or ½" sag resistant when applied to ceilings framed at 24" o/c, IRC table R702.3.5 footnote d.
4. Show 1" air space between sheathing and brick veneer, R703.7.4.2.

PLUMBING PLAN:
5. Provide note requiring that water hammer arrestor be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to: clothes washers, dishwashers, and refrigerators, IRC P2903.5.

MECHANICAL PLAN:
6. Show supply and return air ducts with a minimum R-8 insulation, R1103.2.1.

ELECTRICAL PLAN:
7. Use Table E3605.1 (60 degree C column) for sizing branch circuits and conductors rated <100 amps. Verify wire sizing for the 40 and 50 amp circuits.
8. Show receptacle outlets at wall spaces 2' or more so that no point along the wall (excluding door openings) is more than 6' from a receptacle outlet, E3801.2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
02/13/2009 THAUSER1 OUT TO CUSTOMER Completed
02/13/2009 SUE REEVES REJECT SHELF Completed