Permit Number: T08CM03874
Parcel: 115041630

Address:
738 E MABEL ST

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T08CM03874
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2009 DAVE WITT BUILDING-RESIDENTIAL REVIEW Denied PLAN CHECK COMMENTS - PROJECT #T08CM03874

1/12/09 738 E. MABLE

PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN.

SCOPE OF REVIEW:

THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, IECC AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL.

GENERAL REQUIREMENTS:

1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED
FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE.

2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS.

3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES.


FLOOR PLANS:

1. ALTERNATE ENERGY TECHNOLOGIES' 80 GALLON WATER HEATERS ARE 24" AND 24-1/2" IN DIAMETER AND DOESN'T APPEAR TO FIT IN THE CLOSET.

STRUCTURAL PLANS:

1. PROVIDE MANUFACTURER'S DATA FOR PRE-FAB TRUSSES. TRUSS CALCULATIONS MUST BE SIGNED, DATED AND WET-SEALED BY AN ENGINEER WHO IS REGISTERED IN ARIZONA. TRUSS CALCULATIONS SHALL BE CROSS-REFERENCED TO THE FLOOR PLANS.

2. FRAMING PLAN / 3 ; PLEASE INDICATE WHERE B/3 WILL BE USED. THE BRACE SHOULD GO TO A BLOCK AT THE ROOF DECK ACCORDING TO BCSI - B3. GABLE BRACE ? AN X-BRACE WOULD BE MORE APPROPRIATE.

ELEVATIONS:

1. PLEASE SHOW THE LOCATIONS OF ALL VENTS NEEDED TO COMPLY WITH THE VENTILATION CALCULATIONS FOR THE CRAWL SPACE.

SECTIONS - DETAILS - MISC. NOTES:

1. THE 6X12 APPEARS TO BE LESS THAN 12" ABOVETHE EXPOSED GROUND. R319 (DO YOU WANT TO COVER THE GROUND WITH 6 MIL POLY TO MAKE IT NOT EXPOSED?)

2. NOTE #2 / 1 ; GREEN BOARD AT THE TUB AND SHOWER AREAS IS NO LONGER ACCEPTED BY THEIRC. PLEASE CHANGE THIS NOTE AS INDICATED BY THE NOTE ON THE PLAN. CEMENT BOARD IS ACCEPTED BY THE IRC. R702.4.2

3. PLUMBING NOTE 1 / 1 ; WHERE IS THE SCHEDULE 40 PVC WATER LINE TO BE USED? PLEASE NOTE.

4. FOUNDATION AND CONCRETE NOTE #3 / 4 ; PLEASE CHANGE THE 2003 TO 2006 IRC.

5. MECHANICAL NOTE #1 /4 ; PLEASE CHANGE THE 1994 UMC TO THE 2006 IMC.

MECHANICAL PLANS:

1. WILL THE NEW FAN COIL FOR THE NEW A/C BE IN THE LOCATION OF THE EXISTING UNIT, ON THE ROOF?
IS THE OLD UNIT BEING REPLACED?

ELECTRICAL PLANS:

1. PLEASE PROVIDE A CIRCUIT NUMBER BESIDE EACH ELECTRICAL DEVICE.

OUTDOOR LIGHTING:

1. THE 1380 LUMENS LISTED FOR THE F-1 AND THE F-2 LIGHT FIXTURES EXCEEDS THE 1320 UNSHIELDED LUMENS ALLOWED. WHERE IS THE F-1 FIXTURE LOCATED?







IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER:
DAVE WITT @ 837-4910
12/26/2008 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/16/2009 GERARDO BONILLA OUT TO CUSTOMER Completed
01/16/2009 SUE REEVES REJECT SHELF Completed