Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T08CM03869
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/11/2009 | DAVE WITT | BUILDING-RESIDENTIAL | REVIEW | Denied | PLAN CHECK COMMENTS - PROJECT #T08CM03869 2/12/09 5344 E. 2nd St. PLAN REVIEW FOR THE ABOVE REFERENCED STRUCTURE HAS BEEN COMPLETED. THIS LETTER REFLECTS COMMENTS TO BE ADDRESSED. IN ORDER TO FACILITATE A SHORTER BACK CHECK TIME, WE REQUEST THAT YOU PLEASE PROVIDE REVISED PLANS AND CALCULATIONS, HIGHLIGHTING ANY CHANGES, ALONG WITH A WRITTEN RESPONSE TO EACH OF THE NOTED ITEMS INDICATING ACTION TAKEN. SCOPE OF REVIEW: THE SCOPE OF THIS PLAN REVIEW COVERS ARCHITECTURAL, PLUMBING, MECHANICAL, IECC AND ELECTRICAL CODES. ALL CODE REFERENCES ARE TO THE 2006 IRC AND STATE PLUMBING CODE. ALL FEATURES WERE CHECKED ONLY TO THE EXTENT ALLOWED BY THE SUBMITTALS PROVIDED. ALL PORTIONS OF THIS PROJECT ARE ASSUMED TO MEET OR WILL MEET OTHER DEPARTMENTAL REQUIREMENTS, CONDITIONS AND CONCERNS BEFORE PERMIT APPROVAL. GENERAL REQUIREMENTS: 1. ALL PLANS SHALL BE LEGIBLE AND A SCALE NO SMALLER THAN ΒΌ INCH = 1-FOOT SHALL BE USED FOR ALL FLOOR PLANS, FRAMING PLANS AND ELEVATIONS. DETAILS &CROSS SECTIONS AT A MINIMUM 3/8 INCH = 1-FOOT SCALE. 2. ALL CORRECTIONS AND REVISIONS SHALL BE MADE ON THE ORIGINAL TRACINGS AND TWO NEW SETS OF PRINTS OR (1) SEPIA & (1) BLUE LINE SHALL BE RETURNED ALONG WITH ALL REDLINE PRINTS. 3. PEN OR PENCIL CORRECTIONS ON FINAL PRINTS WILL NOT BE ACCEPTABLE. TO AVOID DELAYS ENSURE ALL CORRECTIONS HAVE BEEN MADE, ARE COMPLETE AND HAVE BEEN COORDINATED ON ALL APPLICABLE DETAILS AND NOTES. FOUNDATION PLANS: 1. THE SHOWER IS REQUIRED TO ACCOMMODATE A 30" DIAMETER CIRCLE ON THE FLOOR AFTER THE WALLS ARE FINISHED. P2708.1 FLOOR PLANS: 1. PLEASE NOTE THAT CEMENT BOARD IS TO BE USED, NOT GREEN BOARD, AS BACKER BOARD FOR THE WALL TILE IN THE SHOWER. R702.4.2 SECTIONS - DETAILS - MISC. NOTES: 1. ROOF SHEATHING NOTE 3 / S2 ; PLEASE CHANGE THE ROOF SHEATHING NAILS TO 8d COMMON. TABLE R602.3(1) ELECTRICAL PLANS: 1. PLEASE PROVIDE A RECEPTACLE AT THE BACK OF THE DWELLING FOR OUTDOOR USE. E3801.7 2. PLEASE ASSIGN THE SMOKE DETECTOR BY THE WATER HEATER TO CIRCUIT 6 TO INTER-CONNECT IT WITH THE OTHERS. OUTDOOR LIGHTING CODE: PLEASE CHECK THE NUMBER OF OUTDOOR LIGHT FIXTURES ON THE EXISTING HOUSE. ONLY ONE IS MENTIONED, BUT HOUSES USUALLY HAVE ONE AT THE FRONT AND ONE AT THE BACK. PLEASE VERIFY. IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR ASSIGNED PLANS EXAMINER: DAVE WITT @ 837-4910 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/20/2009 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 02/20/2009 | SUE REEVES | REJECT SHELF | Completed |