Permit Number: T08CM03850
Parcel: 10511061R

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T08CM03850
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/20/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
12/30/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show that the vacuum relief for the water heater has been installed per the manufacturer's recommendation (i.e. no valve shall be located between the vacuum relef and the water heater).
2. The use of a floor drain as an indirect waste receptor is allowed provided that the drain is equipped with a funnel top to prevent splashing or flooding. Reference: Section 804.1, UPC 2006.
3. The secondary condensate drain shall be piped independently from the primary condensate drain. Reference: Section 307.2.3, IMC 2006.
12/30/2008 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 2; AHU HANGING DETAIL ON SHEET M2: IS THE BEAM CLAMP INDICATED FOR STRUCTURAL BEAMS (AS INDICATED) OR FOR BAR JOISTS (PER VERBAGE)? PLEASE CLARIFY. IS KWIK BOLT ON OPPOSITE SIDE DESIGNED FOR CONNECTION TO STEEL DECK? VERIFY.
12/30/2008 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/20/2009 THAUSER1 OUT TO CUSTOMER Completed