Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T08CM03850
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/20/2009 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
12/30/2008 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show that the vacuum relief for the water heater has been installed per the manufacturer's recommendation (i.e. no valve shall be located between the vacuum relef and the water heater). 2. The use of a floor drain as an indirect waste receptor is allowed provided that the drain is equipped with a funnel top to prevent splashing or flooding. Reference: Section 804.1, UPC 2006. 3. The secondary condensate drain shall be piped independently from the primary condensate drain. Reference: Section 307.2.3, IMC 2006. |
12/30/2008 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PREVIOUS COMMENT 2; AHU HANGING DETAIL ON SHEET M2: IS THE BEAM CLAMP INDICATED FOR STRUCTURAL BEAMS (AS INDICATED) OR FOR BAR JOISTS (PER VERBAGE)? PLEASE CLARIFY. IS KWIK BOLT ON OPPOSITE SIDE DESIGNED FOR CONNECTION TO STEEL DECK? VERIFY. |
12/30/2008 | ROBERT SHERRY | WATER | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
01/20/2009 | THAUSER1 | OUT TO CUSTOMER | Completed |