Permit Number: T08CM03842
Parcel: 140442160

Address:
7668 S WILMOT RD

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T08CM03842
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2009 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
10/06/2009 ROBERT SHERRY WATER REVIEW Denied The water pressure calculations on sheet P3.1 call for a 3" water meter and a 3" reduced pressure principle backflow assembly. Show the size and location of these items on the drawings. (Note that sheet P1.2, 1st floor water piping plan, is not included in the drawing set.) Reference: Section 103.2.3, UPC 2006
10/06/2009 DAVE MANN FIRE REVIEW Denied Provide low level exit signs per IFC 1011.2.
10/07/2009 GERRY KOZIOL WWM REVIEW Denied HOLIDAY INN EXPRESS-53FU'S @COMMERCIAL RATE & 667FU'S @ SFR RATE
NEED TO BUILD PUBLIC SEWER (NEED HOLD HARMLESS LETTER - DSC/ C.C. PATEL - 2ND FLOOR - 740-6586
10/15/2009 SREEVES1 ZONING REVIEW Needs Review
10/15/2009 ELIZABETH LEIBOLD ENGINEERING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/15/2009 SUE REEVES OUT TO CUSTOMER Completed