Permit Number - T08CM03840
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2009 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/27/2009 ERIC NEWCOMB ZONING HC SITE REVIEW Approved
02/11/2009 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The concealed temperature mixer on the specified faucet appears to be a limit stop that does not actively accommodate variations in the temperature of the incoming hot and cold water. Given the temperature range of the water supply in Tucson (as high as 90.3 degrees Fahrenheit), specify how the temperature limit stop on the lavatory faucet is to be adjusted to guarantee a maximum delivery temperature of 110 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.