Permit Number: T08CM03822
Parcel: 105110660

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T08CM03822
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2008 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed Impact Fee's Do Apply; Central District; 10,650 Square Feet; $39,785.15*

*52,852.70 if Permit pulled on or after 1.16.09 which includes police, fire, and public facility fee's
12/09/2008 MARTIN BROWN FIRE REVIEW Approved
12/12/2008 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 12 DECEMBER 2008
T08CM03822/NEXT CARE-URGENT CARE
REVIEWED BY RON BROWN

STRUCTURAL/ACCESSIBLE REVIEW
2006IBC/ICC ANSI 117.1

DENIED: SEE COMMENTS BELOW

A. SHEET A1.0
1. AS PER DSD PERMIT REVIEW STANDARDS, LETTERING FOR ALL DRAWINGS IS TO BE A MINIMUM OF 1/8" IN HEIGHT. 3/32" FONT SIZE MAY BE USED IF APPROVED BY THE BUILDING OFFICIAL. EITHER CHANGE ALL LETTERS TO 1/8" OR PROVIDE AN APPROVED APPEAL FOR 3/32" USAGE FROM THE BUILDING OFFICIAL.
2. UNDER PROJECT INFORMATION CHANGE THE ACCESSIBLE CODE TO 2006 IBC/ICC ANSI 117.1.
3. OCCUPANT LOAD AS PER 2006 IBC, TABLE 1040.1.1 IS BASED UPON GROSS SQUARE FEET WHICH CHANGES YOUR OCCUPANT LOAD FROM 32 TO 42.

B. SHEET A2.1:
1. THE DRINKING FOUNTAIN LAYOUT DESIGN IS NOT THE SAME AS REFERENCED ELECTRIC WATER COOLER DETAIL 7/A6.1. CHANGE FLOOR PLAN TO MATCH CODE COMPLIANT DETAIL AND PROVIDE CLEAR SPACE AS REQUIRED BY ICC ANSI 117.1, SECTION 602.

C. SHEET A4.1:
1. AT DETAIL 4: THE BREAK ROOM SINK NEEDS TO BE 2'-10" ABOVE FINISHED FLOOR.

D. SHEET M0.1:
1. PROVIDE STRUCTURAL CALCULATIONS AND MOUNTING DETAILS FOR THE NEW, ROOF TOP MOUNTED, MECHANICAL UNIT 3.

END OF REVIEW
12/24/2008 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied SEE ATTACHED LETTER
12/30/2008 ROBERT SHERRY WATER REVIEW Approved
12/30/2008 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified drinking fountain (Elkay EZS4) does not meet the accessibility requirements as shown in Section 1109.5, IBC 2006.
2. Provide water supply isometrics. Reference: Section 103.2.3, UPC 2006.
3. Limit the water velocity to less than 8 fps for the copper piping. Reference: Section A 6.1, UPC 2006 and IAPMO IS 3-2003, Section 610.0.
4. Coordinate the call outs for the heat pumps; the mechanical has HP-1(E), HP-2 (E), and HP-3 (N) but the plumbing plan has HP-1 (N), HP-2 (N), HP-3 (E), and HP-4 (E).
12/30/2008 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information to show how the condensate drain system for HP-1 and HP-3 has been sized. Reference: Section 307.2.2, IMC 2006, as amended by the City of Tucson.
12/31/2008 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/12/2009 THAUSER1 OUT TO CUSTOMER Completed
01/12/2009 SUE REEVES REJECT SHELF Completed